Mitsubishi Electric Q64RD User Manual page 48

Thermocouple input module gx configurator-ti (sw1d5c-qtiu-e)
Hide thumbs Also See for Q64RD:
Table of Contents

Advertisement

4 SETUP AND PROCEDURES BEFORE OPERATION
4 - 8
(2) Operating procedure
Start the settings with GX Developer assignment setting screen.
(a) I/O assignment setting screen
Set the following for the slot in which the Q64RD
is mounted.
The type setting is required; set other items as
needed.
Type
: Select "intelli."
Model name : Enter the module model name.
Points
: Select 16 points.
Start XY
: Enter the start I/O number for the
Q64RD.
Detail setting: Specify the control PLC for the
Q64RD.
It is unnecessary to set the "Error
time output mode" or "H/W error
time PLC operation mode" since
these settings are invalid for the
Q64RD.
(b) Switch setting for intelligent function module
screen
Click on [Switch setting] on the I/O assignment
setting screen to display the screen shown at
left, then set switches 1 to 5.
The switches can easily be set if values are
entered in hexadecimal. Change the entry
format to hexadecimal and then enter the
values.
MELSEC-Q
4 - 8

Advertisement

Table of Contents

Troubleshooting

loading

Table of Contents