3 SPECIFICATIONS
Device No.
Signal name
Y1
Y3
CH
Offset
Y5
Setting Request
Y7
Y2
Y4
CH
Gain Setting
Y6
Request
Y8
Operation
Y9
Condition Setting
Request
User Range Write
YA
Request
Error Clear
YF
Request
3 - 9
(2) Output signals
(1) This signal is made valid in the offset/gain setting mode.
(2) This signal corrects the temperature conversion value to be an offset temperature
set value when it is on.
(3) When this signal turns on while the Gain Setting Request on the same channel is on
or they turn on simultaneously, an error will occur and the operation in (2) not
performed.
(4) For the on/off timing, refer to the field of the CH
(X1 to 4).
(1) This signal is made valid in the offset/gain setting mode.
(2) This signal corrects the temperature conversion value to be a gain temperature set
value when it is on.
(3) When this signal turns on while the Offset Setting Request on the same channel is
on or they turn on simultaneously, an error will occur and the operation in (2) not
performed.
(4) For the on/off timing, refer to the field of the CH
(X1 to 4).
(1) This signal is turned on when the "conversion enable/disable designation", "CH
averaging time/count", "averaging processing designation", "warning output
enable/disable designation", "CH
scaling width upper/lower limit value" or "CH
value" is made valid.
(2) When this signal turns on, the Disconnection Detection Flag (XC) and Warning
Output Signal (XD) turn off.
(3) For the on/off timing, refer to the field of the Operation Condition Setting Completed
Signal (X9).
[In offset/gain setting mode]
(1) This turns ON when the value for the adjusted offset/gain settings are registered in
2
the E
PROM.
(2) See the XA column for ON/OFF timing.
See Section 4.6 for offset/gain settings.
[In normal mode]
(1) This signal turns ON when the user range is restored.
(2) Refer to the field of XA for the ON/OFF timing.
Refer to Chapter 7 for user range restoration.
(1) This signal is turned on when the Error Occurred Signal (XF) and Disconnection
Detection Flag (XC) are cleared.
However, the set value error of the intelligent function module switch setting cannot
be cleared. Correct the set value.
(2) For the on/off timing, refer to the field of the Error Occurred Signal (XF).
Description