Chapter 2 TL1 Reference
Set Signal Fault Alarm Parameters
Set Signal Fault Alarm Parameters
These commands set the input error and clear parameters for signal faults on the
specified DS1, E1, or CC Input module or port.
Syntax
SET-PRMTR-AIS:tid:[aid]:ctag::[errcnt],[clrcnt];
SET-PRMTR-BPV:tid:[aid]:ctag::[errcnt],[clrcnt];
SET-PRMTR-CRC:tid:[aid]:ctag::[errcnt],[clrcnt];
SET-PRMTR-LOS:tid:[aid]:ctag::[errcnt],[clrcnt];
SET-PRMTR-OOF:tid:[aid]:ctag::[errcnt],[clrcnt];
Parameter
aid
errcnt
clrcnt
Note:
1
For CC input modules and ports, only the LOS and BPV commands apply; AIS,
CRC, and OOF commands are denied.
Related Commands
Retrieve Signal Fault Alarm
150 SSU-2000e Technical Reference
Format
Sets the alarm level for the specfied Input module [or
SxAy[-z]
1
port].
Specifies the start delay time, which is the number of
0-100: LOS
seconds that the alarm must be present before the alarm
and AIS
message is issued.
0-10000:
OOF, BPV,
and CRC
Specifies the clear delay time, which is the number of
0-100: LOS
error-free seconds after the alarm condition is cleared
and AIS
before the alarm indication is cleared.
0-10000:
OOF, BPV,
and CRC
Parameters, on page 102
Description
12713140-003-2 Revision E.01 – January 2007