ESIE15-13C
4.26 Electronic Thermal (Time Lag)
L8
Remote
Controller
Display
RZQG
Applicable
Models
The error is detected from the current flowing to power transistor into voltage with CT1 (DC
Method of Error
current sensor).
Detection
When compressor overload (except for when startup) is detected.
Error Decision
Conditions
Disconnected compressor coil
Supposed
High pressure is abnormal high
Causes
Defective compressor (if bearing is scratched)
Defective outdoor unit PCB
Stop valve is not opened
Service Diagnosis
Troubleshooting by Remote Controller
161