Daikin RZQG71L9V1 Service Manual page 151

Skyair gqi-eco series heat pump r-410a 50hz smart serues, classic series
Hide thumbs Also See for RZQG71L9V1:
Table of Contents

Advertisement

ESIE15-13C
Service Diagnosis
Diagnosis Flowchart-4
Malfunction of floor temperature
sensor (Detailed Malfunction Code:
CE-04)
Is the connector X9A on the
adapter PC board normally
connected?
YES
Are the connectors of the
sensor itself normally connected?
YES
Check for output from the motion sensor.
Refer to Sensor Address Data No. 26.
(To refer the data, select "3. Remote controller operation procedure"
"3-1. For BRC1E3"
"(4) Operation in service mode")
After checking following the
procedure aforementioned, "--"
does not appear on the
display.
NO
Turn OFF the power supply once, and
then turn it ON again.
CE-04 recurs or "--"
appears on the sensor address
data display.
YES
Troubleshooting by Remote Controller
NO
Properly connect the
connector.
NO
Properly connect the
connector.
YES
Normal operation
NO
Normal operation
Replace the sensor unit.