Troubleshooting by Remote Controller
4.14 High Pressure Abnormality (Detected by the High
Pressure Switch)
E3
Remote
Controller
Display
RZQG71~140
Applicable
Models
Method of Error
[In cooling]
Detect the continuity of high pressure switch (S1PH) with the protection device circuit.
Detection
The error is detected by the outdoor unit intermediate heat exchanger thermistor (R5T).
[In heating]
Detect the continuity of high pressure switch (S1PH) with the protection device circuit.
The error is detected by the indoor unit intermediate heat exchanger thermistor (R3T).
When the high pressure switch is activated (4.0 MPa)
Error Decision
When the outdoor unit intermediate thermistor (R5T) detects the pressure shown below.
Conditions
When the indoor unit intermediate thermistor (R3T) detects the pressure shown below.
Stop valve is not opened
Supposed
Harness breaking or poor connector connection of the high pressure switch
Causes
Defective high pressure switch
Indoor unit suction filter is blocked (In heating)
Defective high pressure switch
Defective indoor unit fan (In heating)
Outdoor heat exchanger is dirt (In cooling)
Defective outdoor unit fan (In cooling)
Overcharge of refrigerant
Defective outdoor unit PCB (A1P)
140
3.92 MPa or more continuously for one minute
(Reference: equivalent saturation temperature 62°C)
3.92 MPa or more continuously for one minute
(Reference: equivalent saturation temperature 62°C)