Indoor Unit Pcb Abnormality - Daikin RZQG71L9V1 Service Manual

Skyair gqi-eco series heat pump r-410a 50hz smart serues, classic series
Hide thumbs Also See for RZQG71L9V1:
Table of Contents

Advertisement

Troubleshooting by Remote Controller
4.4

Indoor Unit PCB Abnormality

A1
Remote
Controller
Display
All models of indoor unit
Applicable
Models
Check data from E
Method of Error
Detection
The error is generated when the data from the E
Error Decision
Conditions
2
E
its content without power. It can be erased, either within the computer or externally and usually
requires more voltage for erasure than the common +5 volts used in logic circuits. It functions
like non-volatile RAM, but writing to E
 Defective indoor unit PCB
Supposed
 External factor (Noise, etc.)
Causes
Troubleshooting
Caution
Be sure to turn off power switch before connect or disconnect connector, or parts damage may be occurred.
Turn OFF the power supply and turn
the power ON again.
Is it normal?
YES
124
2
PROM.
PROM (Electrically Erasable Programmable Read Only Memory): A memory chip that holds
NO
2
PROM is not received correctly.
2
PROM is slower than writing to RAM.
Replace the indoor unit PCB.
The error may be caused by an
external factor, rather than
damaged parts.
Locate the cause and correct
the situation.
ESIE15-13C
Service Diagnosis