Daikin RZQG71L9V1 Service Manual page 178

Skyair gqi-eco series heat pump r-410a 50hz smart serues, classic series
Hide thumbs Also See for RZQG71L9V1:
Table of Contents

Advertisement

Troubleshooting by Remote Controller
Troubleshooting
Caution
Be sure to turn off power switch before connect or disconnect connector, or parts damage may be occurred.
Check the installation conditions.
Is the stop valve open?
YES
Is the difference
between high and low pressure
before startup not more
than 0.2MPa?
YES
Turn OFF the power supply, and then
disconnect the connection between
the compressor and inverter.
CHECK 4
Continuity check in the power
transistor (IGBT). Is the
continuity normal?
YES
The
compressor is grounded and
short circuited.
NO
Refer to P.190.
CHECK 4
164
NO
NO
NO
YES
ESIE15-13C
Open the stop valve.
Insufficient pressure
equalization.
Check refrigerant system.
Replace the outdoor unit PCB
(A1P).
Replace the compressor.
Compressor inspection.
Inspect according to the
diagnosis procedure for
abnormal noises, vibration,
operating status, etc. of the
compressor.
Service Diagnosis