ESIE15-13C
4.23 Outdoor Unit PCB Abnormality
L1
Remote
Controller
Display
RZQG
Applicable
Models
Detect error by current value during waveform output before compressor startup.
Method of Error
Detect error by current sensor value during synchronized operation at the time of startup.
Detection
Detect error using an MP-PAM series capacitor overvoltage sensor.
When over-current is detected at the time of waveform output during operating the
Error Decision
Conditions
When the current sensor error during synchronized operation
When overvoltage occurs in MP-PAM
In case of IGBT error
In case of faulty in E
External factor (Noise, etc.)
Supposed
Defective outdoor unit fan motor
Causes
Broken fuse
Disconnection of compressor
Defective outdoor unit PCB (A1P)
Service Diagnosis
compressor
2
PROM
· IPM failure
· Current sensor failure
· MP-PAM failure
· Defective IGBT or drive circuit
2
· Defective inverter E
PROM
Troubleshooting by Remote Controller
155