ESIE15-13C
2.3
Settings Contents and Code No. for Indoor Units
You can change the setting of 3 x 3 sensing cassette as mentioned below
The method of field setting, which can be conducted through remote controller, is
First
Mode
Code
Description of Setting
No.
No.
Filter
cleaning
0
sign
interval
1
Filter type
Remote controller
2
thermistor
3
Filter cleaning sign
10
7
Detection time for NOT
(20)
(note 4)
presence
Compensation of
8
suction air temperature
(note 5)
in heating mode
Fan OFF at Thermostat
2
OFF
Airflow rate setting
3
during heating
11
(21)
Automatic operation
4
mode control
6
Sensitivity of presence
(note 6)
sensor
0
Option (KRP1B*) output Compressor
Compensation of
7
11
temperature around
(note 6)
(22)
human body
8
Compensation of floor
(note 6)
temperature
Fan speed heating
3
thermostat OFF
12
Automatic restart after
5
(22)
power failure reset
Fan speed cooling
6
thermostat OFF
High air outlet velocity
0
(for high ceiling
applications)
Selection of airflow
1
13
direction
(23)
Flap moving in the
2
swing mode
4 (*2)
Airflow range setting
Field Setting
established practice, but it is possible only with BRCE52 remote controller.
01
Long life
2,500 hrs.
filter
Long
Enabled
Display
30 min
COMPENSATE
(Temperature
[A+2] °C which an
air conditioner
controls when the
temperature of a
remote controller
is A °C)
Normal
Standard
Available
High
Floor sensor does
not work
-4°C
LL-speed
Disabled
LL-speed
Standard
4-way flow
All 4 flaps
synchronized
Upper
Field Setting from Remote Controller
Second Code No.
02
1,250 hrs.
—
Super long
—
Disabled
—
No display
—
60 min
—
NO
COMPENSATION
(Temperature [A]
°C which an air
conditioner
—
controls when the
temperature of a
remote controller
is A °C)
OFF
—
Slightly up
Up
Prohibition
—
Low
Standard
Option
Operation
Higher priority on
the air
Standard
temperature
-2°C
±0°C
Set-speed
—
Enabled
—
Set-speed
—
Slightly up
Up
3-way flow
—
Two opposite
—
flaps
synchronized
Normal
Lower
03
04
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
Sensor does
—
not work
Malfunction
—
Higher
priority on
—
the floor
temperature
+2°C
—
—
—
—
—
—
—
—
—
05
67