Troubleshooting by Remote Controller
4.15 Actuation of Pressure Sensor
E4
Remote
Controller
Display
RZQG
Applicable
Models
Detect the continuity of low pressure switch (S2PL) with the protection device circuit.
Method of Error
[In cooling]
Detection
Detect error by the indoor unit intermediate thermistor (R3T).
[In heating]
Detect error by the intermediate heat exchanger thermistor (R5T).
When the low pressure switch is activated.
Error Decision
When the detection pressure is the following value
Conditions
The stop valve is not opened
Supposed
Disconnection of outdoor unit intermediate thermistor
Causes
Disconnection of indoor unit intermediate thermistor
Defective thermistor
Defective outdoor unit PCB (A1P)
Abnormal drop of low pressure
Refrigerant shortage
142
0.12MPa or less continues for 5 minutes
(When the saturated pressure equivalent temperature is –34°C). This is explain for
"0.12MPa".
ESIE15-13C
Service Diagnosis