Field Setting from Outdoor Unit PCB
3.2

Field Setting for Outdoor Unit

3.2.1 Setting by BS Buttons
With "Setting mode 1," "Setting mode 2" and "Monitor mode," various settings and data can be
checked.
(1) Setting mode 1
The initial status (normal operation) is "Setting mode 1." This mode indicates operating status -
"TEST (test operation)," "HWL (error)," "L.N.O.P (night time quiet operation)" or "DEMAND
(demand operation)."
(2) Setting mode 2
Each operating status can be modified.
(3) Monitor mode
This mode indicates "oil return operation," "outdoor unit class," "contents of retry," "contents of
error," "causes of stepping-down operation," etc.
3.2.2 Setting Mode 1
In this mode, the following conditions can be checked:
These conditions above can be checked by performing the following steps:
The system is normally "Setting mode
1".
Press the MODE (BS1) button once
to set the system to "Setting mode 1".
Check the system for each condition
through LED displays. (Refer to
information in table on the right.)
82
Using the MODE button, the modes can be changed as follows.
Press the BS1 (MODE button)
for 5 seconds or more.
Setting mode 2
Push the BS1(MODE button) one time.
On
H1P
Current operating condition (normal/test operation/line inspection and normal/error)
Night time quiet operation condition (normal/low noise level 1, 2, and)
Demand operating condition (normal/30% demand/40% demand/50% demand)
MODE
TEST HWL
H1P H2P H3P H4P H5P H6P H7P
h
h
h
Initial
(Normal)
Setting mode 1
Off
H1P
k : ON
L.N.O.P
DEMAND
h
h
h
h
During "Setting mode 1," the lamp is always OFF.
Test operation display
h In normal operation
k In test operation
l In line inspection operation
Error display
h Normal
k Error
Night time quiet operation display
hh Normal operation
hk Low noise level 1
kh Low noise level 2
kk Low noise level 3
Demand level display
hh 30% Normal operation
hk 40% Demand
kh 50% Demand
kk Demand
Press the BS1(MODE button)
one time.
Monitor mode
H1P
h : BLINK
l : OFF
ESIE15-13C
Blinking
Field Setting