ESIE15-13C
4.5
Drain Water Level System Abnormality
A3
Remote
Controller
Display
All models of indoor unit
Applicable
Models
By float switch OFF detection
Method of Error
Detection
The error is generated when the water level reaches its upper limit and when the float switch
Error Decision
turns OFF.
Conditions
Defective drain pump
Supposed
Improper drain piping work
Causes
Drain piping clogging
Defective float switch
Defective indoor unit PCB
Defective short circuit connector X15A on PCB
Service Diagnosis
Troubleshooting by Remote Controller