4.41 Check

CHECK 1

Check the Thermistors
Thermistors
If the cause of the problem is related to the thermistors, then the thermistors should be checked
prior to changing the PCB.
For more information about these thermistors, see:
 "Wiring Diagrams'' on P.199
 "Functions of Main Components and Thermistors" on P.28
Overview of Thermistors
The table below contains an overview of the thermistors:
Indoor
FCQG, FHQG
R1T
Suction air thermistor
R2T
Heat exchanger thermistor
R3T
Intermediate heat exchanger thermistor
Outdoor
RZQG
R1T
Outdoor air thermistor
R2T
Discharge pipe thermistor
R3T
Suction pipe thermistor
R4T
Heat exchanger distributor pipe thermistor
R5T
Intermediate heat exchanger thermistor
R6T
Liquid pipe thermistor
R10T
Radiation fin thermistor
Checking
To check the thermistors, proceed as follows:
Step
Action
1
Disconnect the thermistor from the PCB
2
Read the temperature and the resistor value.
3
Check if the measured values correspond with the values in the table on the next pages.
Service Diagnosis
Troubleshooting by Remote Controller
Thermistor
Thermistor
185