Field Setting from Remote Controller
2.6
I-Demand Function
Set a limitation towards the power consumption from the system (e.g. budget control, limit
Purpose
power consumption during peak moments,..).
3 different demand setting can be selected by using terminal X801M:
Setting
Demand 1 Close contact between COM and contact 1
Demand 2 Close contact between COM and contact 2
Demand 3 Close contact between COM and contact 3
Power consumption limitation in function of setting on DS1:
Demand 1
Power consumption limitation set to 40%.
Demand 2
Forced thermostat OFF.
Demand 3
76
Power supply connector
(on outdoor PCB X77A)
X801M
COM
3
2
1
LNOP
DS1 Setting
1
OFF
ON
OFF
ON
DS1
ON
OFF
1 2 3 4
X800M
3
2
1
LNOP COM
2
OFF
OFF
ON
ON
ESIE15-13C
Transmission connector
(on outdoor PCB X6A)
X801M
Output on X801M =
12VDC, 12mA
Maximum wire length =
100 meter
Maximum Power
Consumption
60%
70%
80%
100%
Field Setting