Troubleshooting by Indication on the Remote Controller
3.33 Electronic Thermal (Time Lag)
L8
Remote
Controller
Display
Applicable
RZR, RZQ
Models
Method of Error
The error is detected from the current flowing to power transistor into voltage with CT1 (DC
Detection
current sensor).
Error Decision
When compressor overload (except for when startup) is detected.
Conditions
Compressor overload (during operation)
Supposed
Disconnected compressor coil
Causes
Defective inverter
Defective compressor (if bearing is scratched)
Defective outdoor unit PCB