Daikin RZQG71L9V1 Service Manual page 99

Skyair gqi-eco series heat pump r-410a 50hz smart serues, classic series
Hide thumbs Also See for RZQG71L9V1:
Table of Contents

Advertisement

ESIE15-13C
 Setting of Demand 2 operation
With this setting, compressor operation can be controlled to reduce power consumption.
(60% - 80% demand is available when a demand adapter (optional accessory) is used.)
[Work procedure]
Operating procedure
Push and hold the MODE (BS1) button of "Setting mode 1" for 5 seconds
or more and set to "Setting mode 2."
Push the SET (BS2) button three times to set the LED display as shown
in the table on the right.
Push the RETURN (BS3) button once. (Present settings are displayed.)
Push the SET (BS2) button to set the LED
display as shown in the table on the right.
Push the RETURN (BS3) button once to make a
decision.
Push the RETURN (BS3) button once again for execution. (The LED
display is in the initial status of "Setting mode 2".)
Push the MODE (BS1) button once to return to Setting mode 1 (normal
operation).
Field Setting
Setting item
30% demand
40% demand (factory setting) Operates with 40% of rated
Demand 2 operation
50% demand
Field Setting from Outdoor Unit PCB
Setting condition
Operates with 30% of rated
power consumption.
power consumption.
Operates with 50% of rated
power consumption.
30% of rated power consumption
40% of rated power consumption
50% of rated power consumption
30% of rated power consumption
40% of rated power consumption
50% of rated power consumption
Description
h: OFF l: BLINK k: ON
H1P H2P H3P H4P H5P H6P H7P
k h h h h h h
k h h h h k k
k h h h h l h
k h h h l h h
k h h h h l h
k h h h h h l
k h h h k h h
k h h h h k h
k h h h h h k
k h h h h h h
h h h h h h h