Field Setting from Remote Controller
2.1.3 Remote controller settings
Level
Setting Code Function
1b
8
Automatic summer/
wintertime changeover
a
"Away from Home
function" can be freely
selected in main menu
using RETURN.
You can select start point
for heating between 5°C
and 10°C and for cooling
between 35°C and 40°C.
b
Clock display in the remote
controller
1c
0
Available selection in the
detail display
1
Use remote controller
temperature sensor in
"Detail display", "Away
from Home function" and
"Limit operation"
3
Remote controller keylock
4
Backlighting
6
Display
64
Adjustment Description
Remote controller setting (BRC1E)
01
No automatic changeover
02
Automatic changeover
active
03
Setting menu available in
Extended functions
01
"Away from Home menu" is
not available
02
"Away from Home menu" is
available in main menu
01
Clock is displayed in
remote controller with
detail display ON
02
Clock is not displayed
01
Room temperature not
available
02
Room temperature
available
01
Suction air thermistor
(R1T)
02
Remote controller sensor
01
Level 2
Free keys:
Mode
Setpoint
On/Off
02
Level 3
Free keys:
On/Off
01
Off
02
On as soon as a key is
pressed
03
Permanently On
01
Display is always available
02
Display switches off after 5
minutes and is reactivated
by pressing a key
ESIE15-13C
Info
1x RETURN -> Extended
functions -> Summertime
You must also activate the
"Away from Home
function" in the 1e-2 setting
1x RETURN -> Away from
Home function
Available as from software
04.003
You can determine which
sensors are displayed
using setting 1c-1
1x RETURN -> Extended
functions -> Detail display
If the detail display is
activated, the suction air
thermistor should be used.
To activate or deactivate
the keylock starting 1x right
arrow and then right arrow
again, press Back, Mode,
Fan simultaneously.
4
1
3
2
If the keylock is active, the
key symbol appears when
locked keys are pressed.
Backlight goes out after 20
seconds.