E3 Actuation Of High Pressure Sensor - Daikin VRVII Manual

Vrv series pocket manual
Hide thumbs Also See for VRVII:
Table of Contents

Advertisement

Troubleshooting by Indication on the Remote Controller
E3
3.22
Sensor
Remote Controller Display
E3
Applicable Models
VRVII and II-S Series
Method of Error Detection
Abnormality is detected when the contact of the high
pressure protection switch opens.
Error Decision Conditions
Error is generated when the high pressure switch
activation count reaches the number specific to the
operation mode.
Supposed Causes
Actuation of outdoor unit high pressure switch
Defective high pressure switch
Defective outdoor unit PCB
Instantaneous power failure
Defective high pressure sensor
Actuation of High Pressure
97

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Vrvii 4VrviiiVrvii-sVrviii-qVrviii-sVrv-wii

Table of Contents