Alarm - Danfoss ECL Comfort 310 Operating Manual

Application a333
Hide thumbs Also See for ECL Comfort 310:
Table of Contents

Advertisement

Operating Guide ECL Comfort 310, application A333

5.16 Alarm

The alarm function activates A1 (relay 6). The alarm relay can
activate a lamp, a horn, an input to an alarm transmitting device etc.
The alarm relay is activated
as long as the alarm reason is present (automatic reset) or
even the alarm reason has disappeared (manual reset)
Alarm, possibilities:
Name:
Description:
Temp.
Actual flow temperature
monitor
differs from the desired flow
temperature.
Refill tank
Too low or too high water level
(A333.2,
in refill water storage tank.
A333.3)
S7 . . . S10
Too low or too high pressure.
pressure
Low
Too low pressure at S10.
pressure
Temperature
Accidently break or
sensor input
short-circuit of connected
temperature sensor.
MENU > Settings > Alarm
Upper difference
The alarm is activated if the actual flow / duct temperature increases more
than the set difference (acceptable temperature difference above the desired
flow / duct temperature). See also 'Delay' .
See Appendix "Parameter ID overview"
OFF:
The related alarm function is not active.
Value:
The alarm function is active if the actual temperature
gets above the acceptable difference.
124 | © Danfoss | 2017.09
Reset:
Automatic
Resetting an alarm, in general:
MENU > Alarm > Alarm overview: Look for alarm symbol in specific
line.
Manual
(Example: "3: Pump 1")
Push dial
Automatic
Automatic
Manual
Upper difference
1x147
X
Y
# 1 #
# 2 #
=
Time
=
Temperature
=
Upper difference
=
Desired flow temperature
VI.GU.T2.02