Operating Guide ECL Comfort 310, application A333
MENU > Settings > Alarm
Alarm time-out
Circuit
1
If an alarm condition from either 'Alarm high' or 'Alarm low' is present for
a longer time than the set Alarm time-out (in minutes), the alarm function
is activated.
0 - 100:
Set the time-out time.
MENU > Settings > Alarm
Alarm low
Circuit
1
Alarm is activated when the pressure (in bar) at S10 gets lower than the
set value.
See also "Alarm time-out" (ID no. 15617).
0.0 - 25.0: Set the low alarm level
MENU > Settings > Alarm
Alarm time-out
Circuit
1
If the alarm condition from 'Alarm low' is present for a longer time than the
set Alarm time-out (in seconds), the alarm function is activated.
See also "Alarm low" (ID no. 15615).
0 - 100:
Set the time-out time.
128 | © Danfoss | 2017.09
1x617
Setting range
Factory setting
0 . . . 100 m
15615
Setting range
Factory
setting
0.0 . . . 25.0 bar
25.0 bar
15617
Setting range
Factory setting
0 . . . 250 s
10 m
When the "Low pressure" alarm is activated:
*
the alarm symbol appears in the display
*
the control valve M1 closes
*
the circulation pump stops
If the "Low pressure" alarm reason disappears:
*
the alarm symbol disappears in the display
*
the control valve M1 works normal
*
the circulation pump starts
10 s