Danfoss ECL Comfort 310 Operating Manual page 104

Application a333
Hide thumbs Also See for ECL Comfort 310:
Table of Contents

Advertisement

Operating Guide ECL Comfort 310, application A333
MENU > Settings > Refill water
Change duration
Circuit
1
The number of days between refill water pump change-over.
OFF:
The automatic refill water pump change-over is disabled.
1 - 60:
The automatic refill water pump change-over is enabled.
MENU > Settings > Refill water
Pressure des.
Circuit
1
Setting of desired pressure at S10 in order to ON / OFF control the refill
pump(s) P3 / P4.
See also 'Pressure diff. '
0.2 - 25.0: Set the desired pressure at S10.
104 | © Danfoss | 2017.09
Setting range
Factory setting
OFF / 1 . . . 60 days
Setting range
Factory setting
0.2 . . . 25.0 bar
12311
7 days
= Time
X
# 1 # = Change duration
The "Change duration" has no influence when only one refill water
pump is selected in "No. of pumps" (ID no. 11326).
11321
The parameter "Pressure des." is also used in application A333.2 /
3.0 bar
A333.3 for setting desired pressure for speed controlled refill pump(s)
P3 / P4.
VI.GU.T2.02