Danfoss ECL Comfort 310 Operating Manual page 114

Application a333
Hide thumbs Also See for ECL Comfort 310:
Table of Contents

Advertisement

Operating Guide ECL Comfort 310, application A333
MENU > Settings > Application
DHW priority (closed valve / normal operation)
The heating circuit can be closed when the controller acts as slave and when
DHW heating / charging is active in the master.
See Appendix "Parameter ID overview"
OFF:
The flow temperature control remains unchanged
during active DHW heating / charging in the master
controller.
ON:
The valve in the heating circuit is closed* during active
DHW heating / charging in the master controller.
* The desired flow temperature is set to the value set in
'Frost pr. T'
MENU > Settings > Application
P frost T (circulation pump, frost protection temp.)
Frost protection, based on the outdoor temperature.
When the outdoor temperature gets below the set temperature value in 'P
frost T' , the controller automatically switches ON the circulation pump (for
example P1 or X3) to protect the system.
See Appendix "Parameter ID overview"
OFF:
No frost protection.
Value:
Circulation pump is ON when the outdoor temperature
is below the set value.
MENU > Settings > Application
P heat T (heat demand)
When the desired flow temperature is above the set temperature in 'P heat T' ,
the controller automatically switches ON the circulation pump.
See Appendix "Parameter ID overview"
Value: The circulation pump is switched ON when the desired
flow temperature is above the set value.
MENU > Settings > Application
Frost pr. T (frost protection temperature)
Circuit
Set the desired flow temperature for example at heating cut-out, total stop
etc. to protect the system against frost.
5 ... 40: Desired frost protection temperature.
114 | © Danfoss | 2017.09
1x052
1x077
1x078
11093
Setting range
Factory setting
5 ... 40 °C
10 °C
This setting must be considered if this controller is a slave.
Under normal conditions, your system is not frost protected if your
setting is below 0 °C or OFF.
For water-based systems, a setting of 2 °C is recommended.
If the outdoor temperature sensor is not connected and the factory
setting has not been changed to 'OFF' , the circulation pump is always
ON.
The valve is fully closed as long as the pump is not switched on.
VI.GU.T2.02