Danfoss ECL Comfort 310 Operating Manual page 101

Application a333
Hide thumbs Also See for ECL Comfort 310:
Table of Contents

Advertisement

Operating Guide ECL Comfort 310, application A333
MENU > Settings > Pump control
Retry time
Circuit
1
If an alarm has been generated for the pump or alarms have been generated
for both pumps, this setting will determine the time between the time of the
alarm and the retry time for repeated pump start.
OFF:
No retry time required after an alarm. The pump or
pumps in question will not be restarted.
1 ... 99:
After an alarm, the pump or pumps will be restarted
after the set time.
MENU > Settings > Pump control
Stab. time (stabilization time)
Circuit
1
Setting of max. time to elapse between pump start command and feedback
from differential pressure switch.
If the differential pressure switch does not give feedback within the set time,
the alarm will be activated and the other pump will get a start command.
MENU > Settings > Pump control
Change, duration
Circuit
1
The number of days between shift of circulation pumps. The shift takes place
at the time set in 'Change time' .
VI.GU.T2.02
11310
Setting range
Factory setting
OFF / 1... 99 m
OFF
11313
Setting range
Factory setting
1... 99 s
50 sec
11311
Setting range
Factory setting
1 . . . 10 days
7 days
If the chosen stabilization time ('Stab. time') is too short, the active
pump will stop immediately after the stabilization time has elapsed.
= Time
X
# 1 # = Change duration
© Danfoss | 2017.09 | 101