Danfoss ECL Comfort 310 Operating Manual page 147

Application a333
Hide thumbs Also See for ECL Comfort 310:
Table of Contents

Advertisement

Operating Guide ECL Comfort 310, application A333
When ECA 30 / 31 is in ECA MENU mode, the date and measured
room temperature is displayed.
ECA MENU > ECA settings > ECA sensor
Room T Offset
Setting range
–10.0 ... 10.0 K
The measured room temperature can be corrected
with a number of Kelvin. The corrected value is used
by the heating circuit in the ECL controller.
Minus
The indicated room temperature is lower.
value:
0.0 K:
No correction of the measured room temperature.
Plus
The indicated room temperature is higher.
value:
ECA MENU > ECA settings > ECA sensor
RH offset (ECA 31 only)
Setting range
–10.0 ... 10.0 %
The measured relative humidity can be corrected
with a number of %-values. The corrected value is
used by the application in the ECL controller.
Minus
The indicated relative humidity is lower.
value:
0.0 %:
No correction of the measured relative humidity.
Plus
The indicated relative humidity is higher.
value:
ECA MENU > ECA system > ECA display
Backlight (display brightness)
Setting range
0 ... 10
Adjust the brightness of the display.
0:
Weak backlight.
10:
Strong backlight.
VI.GU.T2.02
Factory setting
0.0 K
Factory setting
0.0 %
Factory setting
5
Example:
Room T offset:
Displayed room temperature:
Room T offset:
Displayed room temperature:
Example:
RH offset:
Displayed relative humidity:
RH offset:
Displayed relative humidity:
0.0 K
21.9 °C
1.5 K
23.4 °C
0.0 %
43.4 %
3.5 %
46.9 %
© Danfoss | 2017.09 | 147

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents