Operating Guide ECL Comfort 310, application A333
ECA MENU > ECA system > ECA override
Override circuit
Setting range
OFF / 1 ... 4
The feature 'Override' (to extended comfort or
saving period or holiday) must be addressed to the
heating circuit in question.
OFF:
No heating circuit is selected for override.
1 ... 4: The heating circuit number in question.
ECA MENU > ECA system > ECA version
ECA version (read-out only), examples
087H3200
Code no.
Hardware
A
1.42
Software
5927
Build no.
13579
Serial no.
23.2012
Production week
The ECA version information is useful in service situations.
150 | © Danfoss | 2017.09
Factory setting
OFF
The circuit in question for override in the ECL controller must be in
scheduled mode.
See also the parameter 'Override addr.' .
Example 1:
(One ECL controller and one ECA 30 / 31)
Override of heating
Set 'Connection addr.' to
circuit 2:
15
Example 2:
(Several ECL controllers and one ECA 30 / 31)
Override of heating
Set 'Connection addr.' to 6 Set 'Override
circuit 1 in ECL
controller with the
address 6:
Quick guide "ECA 30 / 31 to override mode":
1. Go to ECA MENU
2. Move cursor to "Clock" symbol
3. Select the "Clock" symbol
4. Choose and select one of 4 override functions
5. Below the override symbol: Set hours or date
6. Below hours / date: Set desired room temperature for the override
period
Set 'Override
circuit' to 2
circuit' to 1
VI.GU.T2.02