Operating Guide ECL Comfort 310, application A333
MENU > Settings > Flow / power limit
Filter constant
The value of the filter constant determines the dampening of the measured
value.
The higher the value, the more dampening.
By this, a too quick change of the measured value can be avoided.
See Appendix "Parameter ID overview"
Minor
Lower dampening
value:
Major
Higher dampening
value:
MENU > Settings > Flow / power limit
Input type
Choice of M-bus signal from energy meter number 1 ... 5. Only possible
in ECL Comfort 310.
OFF:
No M-bus signal acquired.
EM1 ... EM5: Energy meter number.
MENU > Settings > Flow / power limit
Units
Choice of units for measured values.
See Appendix "Parameter ID overview"
Units to the left: pulse value.
Units to the right: actual and limitation values.
The value from the flow meter is expressed as ml or l.
The value from the energy meter is expressed as Wh, kWh, MWh
or GWh.
The values for the actual flow and the flow limitation are expressed
as l/h or m³/h.
The values for the actual power and the power limitation are
expressed as kW, MW or GW.
VI.GU.T2.02
1x113
11109
Flow or power limitation is based on M-bus signal (ECL Comfort 310
controllers only).
1x115
List for setting range of 'Units':
ml, l/h
l, l/h
ml, m³/h
l, m³/h
Wh, kW
kWh, kW
kWh, MW
MWh, MW
MWh, GW
GWh, GW
Example 1:
'Units' (11115):
'Pulse' (11114):
Each pulse represents 10 litres and the flow is expressed as cubic
meters (m³) per hour.
Example 2:
'Units' (11115):
'Pulse' (11114):
Each pulse represents 1 kilo Watt hour and the power is
expressed in kilo Watt.
l, m³/h
10
kWh, kW (= kilo Watt hour, kilo Watt)
1