Operating Guide ECL Comfort 310, application A333
MENU > Settings > Alarm
Alarm time-out (A333.2 / A333.3)
Circuit
1
If an alarm condition from either 'Alarm high' or 'Alarm low' is present for
a longer time than the set Alarm time-out (in seconds), the alarm function
is activated.
See also: "Alarm high" (ID no. 16614) and "Alarm low" (ID no. 16615).
0 - 250:
Set the time-out time.
ID no. overview for S7, S8, S9 and S10 alarm:
Alarm high
S7
14614
13614
S8
12614
S9
11614
S10
MENU > Settings > Alarm
Alarm high
Circuit
Setting range
1
0.0 . . . 25.0 bar
Alarm is activated when the pressure (in bar) gets higher than the set value.
0.0 - 25.0: Set the high alarm level
MENU > Settings > Alarm
Alarm low
Circuit
1
Alarm is activated when the pressure (in bar) gets lower than the set value.
0.0 - 25.0:
Set the low alarm level.
VI.GU.T2.02
Setting range
Factory setting
0 . . . 250 s
Alarm low
Alarm time-out
14615
14617
13615
13617
12615
12617
11615
11617
Factory setting
25.0 bar
Factory setting
Setting range
0.0 . . . 25.0 bar
25.0 bar
16617
15 s
= Time
X
= Level
Y
# 1 # = Actual level
# 2 # = Alarm high
# 3 # = Alarm low
# 4 # = Alarm time-out
1x614