Operating Guide ECL Comfort 310, application A333
MENU > Settings > Refill water
Pressure diff.
Circuit
1
Setting of the switching difference for the measured pressure at S10.
The difference is symmetrical around the 'Pressure des. '
See also 'Pressure des. '
0.1 - 5.0: Set the desired switching difference related to the
pressure at S10.
MENU > Settings > Refill water
Max. pressure
Circuit
1
Setting of the max. acceptable pressure at S10.
When the pressure at S10 gets higher than set value, the release valve V2 is
opened in order to reduce the pressure.
See also "Max. press. diff. "
0.0 - 40.0: Set the max. acceptable pressure at S10.
VI.GU.T2.02
13322
Setting range
Factory setting
0.1 . . . 5.0 bar
1.5 bar
11318
Factory setting
Setting range
0.0 . . . 40.0 bar
40.0 bar
= Time
X
= Pressure
Y
# 1 # = Pressure desired
# 2 # = Actual pressure
# 3 # = Pressure difference
= Time
X
= Pressure
Y
# 1 # = Max. pressure
# 2 # = Actual pressure
# 3 # = Max. pressure difference