Danfoss ECL Comfort 310 Operating Manual page 96

Application a333
Hide thumbs Also See for ECL Comfort 310:
Table of Contents

Advertisement

Operating Guide ECL Comfort 310, application A333
MENU > Settings > Control parameters, refill pump(s)
Wake up level (A333.2 / A333.3)
Circuit
1
After elapse of the "Sleep mode" time and a continued refill demand, the
refill water pump restarts with a speed level as the set value.
See also: "Sleep level" and "Sleep mode time".
0 - 100:
Set the restart speed level
MENU > Settings > Control parameters, refill pump(s)
Boost (A333.2 / A333.3)
Circuit
1
The "Wake-up level" can be increased with a % value.
0 - 100:
Set the boost level
96 | © Danfoss | 2017.09
11330
Setting range
Factory setting
0 . . . 100 %
40 %
11333
Setting range
Factory setting
0 . . . 100 %
5 %
Example:
"Wake-up level" = 40 %
"Boost" = 15 %
Result: The increased "Wake-up level" = 40 x 1.15 = 46 %
VI.GU.T2.02

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents