(4) Transmission cable specifications

(4)-1 Transmsson cables
PWFY-P100VM-E-BU
Transmsson cables
Sheldng wre (2-core)
Type of cable
CVVS, CPEVS or MVVS
More than 1.25 mm
Cable dameter
Remarks
PWFY-P100, 200VM-E-AU
Transmsson cables
Sheldng wre (2-core)
Type of cable
CVVS, CPEVS or MVVS
More than 1.25 mm
Cable dameter
Remarks
*1 Connected with simple remote controller. CVVS, MVVS: PVC insulated PVC jacketed shielded control cable
(5) Connectng electrcal connectons
Verfy that the model name on the operatng nstructons on the cover of the control box s the same as the model name
on the nameplate.
Step 1
Remove the screws holdng the termnal box cover n place.
[Fg. V.1.(5).1]
(A)
Note:
Ensure that the wiring is not pinched when fitting the terminal box cover. Pinching the wiring may cut it.
Caution:
Install wiring so that it is not tight and under tension. Wiring under tension may break, or overheat and burn.
Fx power source external nput/output lne wrng to control box by usng buffer bushng for tensle force to prevent
electrc shock. (PG connecton or the lke.) Connect transmsson wrng to transmsson termnal block through the
knockout hole of control box usng ordnary bushng.
After wrng s complete, make sure agan that there s no slack on the connectons, and attach the cover onto the
control box n the reverse order removal.
[Fg. IV. 1.(5).2]
(A)
(B)
(C)
(D)
(E)
(G)
Caution:
Wire the power supply so that no tension is imparted. Otherwise disconnection, heating or fire result.
MA Remote controller cables
Sheathed 2-core cable (shelded)
2
0.3 ∼ 1.25 mm
-
Max.length: 200 m
MA Remote controller cables
Sheathed 2-core cable
CVV (unshelded)
2
0.3 ∼ 1.25 mm
-
Max.length: 200 m
CVV, MVV
CPEVS
(C)
(B)
(A) To prevent external tensle force from applyng to the wrng
(B) External signal input cable
(A)
(C) External sgnal output cable
(D) Power source wrng
(A)
(E) Tensle force
(F) Use ordnary bushng
(G) Transmission cable and MA remote controller cable
(F)
Sheathed mult-core cable (shelded)
CVVS
2
2
(0.75 ∼ 1.25 mm
)*1
Max.length: 100 m
Sheathed mult-core cable
CVV or MVV (unshielded)
2
2
(0.75 ∼ 1.25 mm
)*1
Max.length: 100 m
: PVC insulated PVC sheathed control cable
: PE nsulated PVC jacketed shelded communcaton cable
(A) Screws
(B) Front panel
(C) Control box
connecton secton of power source termnal block use buffer
bushng lke PG connecton or the lke.
- 44 -
External nput
Sheathed mult-core cable (unshelded)
CVVS or MVVS
2
0.3 ∼ 0.5 mm
Rated voltage: L1-N: 220 ∼ 240 V
External nput
Sheathed mult-core cable (unshelded)
2
0.3 ∼ 0.5 mm
Rated voltage: L1-N: 220 ∼ 240 V
External output
CVV or MVV
2
0.3 ∼ 1.25 mm
Rated load: 0.6 A
External output
CVV or MVV
2
0.3 ∼ 1.25 mm
Rated load: 0.6 A