10
The Synchronization Dialog Box
is displayed.
Confirm that the data to transfer
(NJ501 in the right figure) is
selected. Then, click the
Transfer to Controller Button.
11
A confirmation dialog is
displayed. Click the Yes Button.
A screen stating "Synchronizing"
is displayed.
A confirmation dialog box is
displayed. Click the No Button.
12
Confirm that the synchronized
data is displayed with the color
specified by "Synchronized",
and that a message is displayed
stating "The synchronization
process successfully finished".
If there is no problem, click the
Close Button.
Additional Information
If the synchronization fails, referring to the message that is displayed, please take
appropriate action. For details, refer to 10-3 Error Messages for Sysmac Studio Operation in
the Sysmac Studio Version 1 Operation Manual (Cat. No. W504).
7.Connection Procedure