Omron NJ501 Connection Manual page 18

Machine automation controller nj-series; ne1a-series safety network controller
Hide thumbs Also See for NJ501:
Table of Contents

Advertisement

7.3.3.
Setting Global Variables
Set global variables used for the remote I/O communications.
1
Double-click Global variables
under Programming - Data in
the Multiview Explorer.
2
The Global Variables Tab is
displayed in the Multiview
Explorer.
Click a column under Name to
enter a new variable.
Enter DN00_Area2_OUT in the
Name Column.
Enter WORD in the Data Type
Column.
Enter %3200 in the AT Column.
3
After entering, right-click and
select Create New from the
menu.
4
Enter the following data in the
new columns in the same way
as steps 2 and 3.
•Name: DN00_Status_IN
Data Type: BOOL[32]
AT: %3300
*After entering,
ARRAY[0..31] OF BOOL is
displayed as shown on the
right figure.
•Name: DN00_Area1_IN
Data Type: WORD
AT: %3302
7.Connection Procedure