Abnormal Codes Returned During Communication Using Mc Protocol - Mitsubishi Electric FX3U-ENET User Manual

Hide thumbs Also See for FX3U-ENET:
Table of Contents

Advertisement

11
TROUBLESHOOTING

11.4.3 Abnormal codes returned during communication using MC protocol

Error code
Error
(hexadecimal)
10
PC number error
H
11
Mode error
H
18
Remote error
H
11 - 20
This section explains the abnormal codes (error codes) that are added to responses
when communicating using MC protocol (An abnormal code is added only when an
end code is "5B".)
For more details on the end codes (error codes) that are added to responses, see
Subsection 11.4.2.
For more details on the end codes (error codes) that are stored in the buffer memory
of the Ethernet module, see Subsection 11.4.4.
Response format
Subheader
Description of error
The PC number designated was not "FF".
Poor communication between the Ethernet module and the PLC
(1)After the Ethernet module receives a request successfully from an
external device, the Ethernet module and the PLC could not
communicate for some reason (noise, etc.).
Remote RUN/STOP not accessible.
The PLC base module status is CPU ERR or PROG ERR.
End code
Abnormal code
When an abnormal code is stored, the end code is "5B
(1)Set the PC number to "FF"..
(1)Communicate again. If an error occurs again,
check noise, etc. and replace the Ethernet
module, then communicate again.
(1)Check whether or not the base module has a
CPU ERR (light on) or PROG ERR (flashing
light).
MELSEC-F
00
H
Corrective action
11 - 20
."
H