Mitsubishi Electric FX3U-ENET User Manual page 55

Hide thumbs Also See for FX3U-ENET:
Table of Contents

Advertisement

3
SPECIFICATIONS
BFM number
Attribute
Decimal
(Hexadecimal)
24320
R/W
(5F00
)
H
24321
R/W
(5F01
)
H
24322, 24323
(5F02, 5F03
)
H
Mail Function
24324 to 24355
R/W
(5F04 to 5F23
)
H
24356 to 24387
R/W
(5F24 to 5F43
)
H
24388
R/W
(5F44
)
H
24389 to 24575
(5F45 to 5FFF
)
H
24576 to 31799
System area
(6000 to 7C37
)
H
*2 The mail function of BFM#24320 to #24575 is supported in Ethernet modules V. 1.10 or later.
(This area is inaccessible in V 1.01 or earlier because it is handled as the system area.)
3 - 27
Application
SMTP server port number
(Fixed to "25" in devices earlier than V. 1.01)
SMTP authentication setting
0: No authentication
1: SMTP-AUTH
2: POP before SMTP
Any other value is handled as "0".
System area
*2
SMTP login ID (64 characters)
SMTP password (64 characters)
POP3 server port number
(Fixed to "110" in devices earlier than V. 1.01)
System area
Name
MELSEC-F
(Continued from the previous page)
Initial value
Flash ROM
Reference
Decimal
save
(Hexadecimal)
25
Section 10.6
(19
)
H
0
Section 10.6
(0
)
H
"\0"
Section 10.6
"\0"
Section 10.6
110
Section 10.6
(6E
)
H
(Continues on the next page)
section
3 - 27

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Fx3u-enet-l

Table of Contents