Mitsubishi Electric FX3U-ENET User Manual page 123

Hide thumbs Also See for FX3U-ENET:
Table of Contents

Advertisement

6
FIXED BUFFER COMMUNICATION (WITH THE PROCEDURE EXIST
CONTROL METHOD)
Initial processing normally
completed BFM#=0001
H
HUB connection is signal
BFM #28 b7
OPEN/CLOSE instruction status
BFM#1602=0005
H
Write the send data word
count and the send data
in BFM
Fixed buffer send instruction
and transmission completion
BFM#1610
6 - 4
Initial
Open
Send data
processing
processing
writing
1)
2)
3)
4)
TO
1) Confirm the normal completion of the initial processing.
2) Confirm that the link status is normal between the Ethernet module and
the connected HUB.
3) Confirm the normal completion of the open processing of connection
No. 1
4) Write the send data word count and the send data in the fixed buffer data
area (communication address setting area: BFM#1664 to 2687) by TO
instruction. (In program example, the MOV instruction and the BMOV
instruction are used.)
5) Write "0001
" in the fixed buffer communication transmission request
H
(BFM#1610).
6) The size of send data in the fixed buffer (No. 1) area designated by the
send data length is sent to the designated external device (set in the
open processing).
The value in BFM#1610 becomes "0002
7) Upon receiving the data from the Ethernet module, the external device
returns a "Response" to the Ethernet module.
8) Upon receiving the "Response" from the external device, the Ethernet
module ends the data transmission.
If the "Response" is not returned within the response monitoring time
values (see Section 5.2), a data send error occurs.
At normal completion
Fixed buffer transmission result (BFM#1610)
At abnormal completion
Fixed buffer transmission result (BFM#1610)
If the data transmission is abnormally completed, execute the send
process again writing "0001
Data sending
Response
receiving
8)
5)
W
R
0001
0002
H
H
7)
6)
H
" in BFM#1610.
H
MELSEC-F
R
0004
(Success)/0008
(Error issued)
H
H
".
: 0004
H
: 0008
H
6 - 4