9 Technical Specification
Features
Features
Automatic measurements of Voltage, Turns Ratio, Current, and Phase displacement
•
Turns ratio range 0.8 to 16000
•
Easy one time hook up to the transformer
•
Automatic test voltage range
•
Displays deviation from a nominal ratio
•
Graphical tap changer display
•
Tap changer interface (In- and Output)
•
Load on test object <0.05 VA
•
Measures Power transformers PT's and CT's
•
Displays % error vs. name plate value
•
Automatic phase vector detection
•
Enhanced heavy-duty protection circuitry
•
Extremely rugged (withstands a drop test of 1 meter)
•
Data exchange with USB-Key
•
Internal Printer
•
Measurement Parameters
Ratio:
Resolution: 5 Digits
100V, Range
40V
0.8 ... 2000
2001 ... 4000
4001 ... 13000 ±0.3%
13000 ... 16000 ±0.4%
10V
Range
0.8 ... 500
501 ... 1000
1001 ... 3250
3251 ... 4000
1V
Range
0.8 ... 50
51 ... 100
101 ... 325
326 ... 400
Current
Range
0 ... 1A
90100.1.02 Instruction Manual TR-MARK III
Accuracy at 100 V or 40 V
±0.06% Rdg ±1 LSD
±0.1%
Rdg ±1 LSD
Rdg ±1 LSD
Rdg ±1 LSD
Accuracy at 10 V
0.1%
±
Rdg ±1 LSD
0.12%
±
Rdg ±1 LSD
0.3%
±
Rdg ±1 LSD
0.4%
±
Rdg ±1 LSD
Accuracy at 1 V
0.1%
±
Rdg ±1 LSD
0.15%
±
Rdg ±1 LSD
0.3%
±
Rdg ±1 LSD
0.4%
±
Rdg ±1 LSD
Accuracy
Resolution
±0.001 A
0.1mA
Page 46 of 70