4.2.2 Comparison of International Standards
High Winding Side:
Wire Color
ANSI
RED
H1
BLACK
H2
BLUE
H3
YELLOW
H0
Low Winding Side:
Wire Color
ANSI
RED
X1
BLACK
X2
BLUE
X3
YELLOW
X0
NOTE
⇒ This manual refers to the ANSI standards for all examples. To change
WARNING!
⇒ BEFORE OPERATING THIS OR ANY OTHER TEST EQUIPMENT
⇒ DO NOT VARY INPUT VOLTAGE (MAINS) AFTER POWERING ON
⇒ The TR-MARK III auto-senses the input (mains) voltage from 100 TO
⇒ The TR-MARK III then "locks–in" the test voltage range. If the input
90100.1.02 Instruction Manual TR-MARK III
Wire Color
RED
BLACK
BLUE
YELLOW
Wire Color
RED
BLACK
BLUE
YELLOW
the standard in the test instrument please refer to chapter '8.5.3
Standards'.
READ ALL SAFETY WARNINGS AND UNDERSTAND THEM FULLY.
TEST SET.
240 VAC 50 / 60 Hz.
voltage (mains) is varied after the TR-MARK III was powered on the
actual test voltage may be higher or lower than indicated and system
may get damaged
IEC
Wire Color
U
RED
V
YELLOW
W
BLUE
N
BLACK
IEC
Wire Color
u
RED
v
YELLOW
w
BLUE
n
BLACK
Australian
A
B
C
N
Australian
a
b
c
n
Page 14 of 70