5.2 Setting the times-of-use

You can enter three time periods for the time-controlled operation for every day of the week,
during which the heating system runs in rated operation.
The default setting is a daily rated operation with just one period of time-of-use from 7:00 to
22:00 hrs.
During this time period, the heating system runs dependent on the predetermined operating
mode: weather-compensated according to the set heating characteristic or over a fixed flow
set point.
The heating system is switched over to reduced operation when the time-of-use period ends.
This saves energy in the times of non-use, e.g. at night time.
The heating system runs with a lower reference value during reduced operation.
You can set the reference value for room temperature directly after setting the times-of-use
(chapter 5.3).
The heating system switches back to rated operation again when the reduced operation ends.
You can enter the three time-of-use periods (1, 2 and 3) weekly (1 to 7) with the same time
schedule daily or on a day-to-day basis (1, 2, 3 etc.).
Note:
If you want to enter time-of-use periods that are different on just one day or on a few days of
the week, first select the week entry with the same time schedule daily. Then turn the control
knob until the day, which should have different times-of-use, appears in a box at the top of
the display. Enter the new schedule. When you enter a new schedule, you write over the
weekly entered times-of-use on the selected day.
Caution:
If you select the week entry to enter schedule, you write over all time-of-use periods that have
already been entered.
Note: An optimize function is included in the controller. This function makes sure that the con-
troller automatically switches the heating circuit to the reference value or set point that ap-
plies to the time-of-use at least 59 minutes before it starts dependent on the outdoor tempera-
ture. The sun symbol blinks in the display when this function becomes effective.
If you are not on the user level, press the control knob for
three seconds.
First of all, the time appears in the display.
Setting options on the user level