Danfoss VLT AutomationDrive FC 360 Quick Manual page 46

Hide thumbs Also See for VLT AutomationDrive FC 360:
Table of Contents

Advertisement

Applications
FC
+24 V
12
18
D IN
D IN
19
27
D IN
29
D IN
D IN
31
D IN
32
D IN
33
+10 V
50
A IN
53
6
6
A IN
54
COM
55
A OUT
42
Table 6.12 Speed Up/Speed Down
Speed
Reference
Start (18)
Freeze ref (27)
Speed up (29)
Speed down (32)
Illustration 6.1 Speed Up/Speed Down
44
®
VLT
AutomationDrive FC 360
Parameters
Function
Setting
Parameter 5-10 T
erminal 18
*[8] Start
Digital Input
Parameter 5-12 T
[19] Freeze
erminal 27
Reference
Digital Input
Parameter 5-13 T
[21] Speed Up
erminal 29
Digital Input
Parameter 5-14 T
[22] Speed
erminal 32
Down
Digital Input
*=Default value
Notes/comments:
Danfoss A/S © 03/2017 All rights reserved.
6.2.4 Start/Stop
FC
+24 V
12
18
D IN
D IN
19
27
D IN
29
D IN
D IN
31
D IN
32
D IN
33
+10 V
50
A IN
53
A IN
54
COM
55
A OUT
42
Table 6.13 Start/Stop with Reversing and 4 Preset Speeds
Parameters
Function
Setting
Parameter 5-10 Ter
minal 18 Digital
*[8] Start
Input
Parameter 5-11 Ter
*[10]
minal 19 Digital
Reversing
Input
Parameter 5-12 Ter
[0] No
minal 27 Digital
operation
Input
Parameter 5-14 Ter
[16] Preset
minal 32 Digital
ref bit 0
Input
Parameter 5-15 Ter
[17] Preset
minal 33 Digital
ref bit 1
Input
Parameter 3-10 Pre
set Reference
Preset ref. 0
25%
Preset ref. 1
50%
Preset ref. 2
75%
Preset ref. 3
100%
*=Default value