Applications
Parameter 6-91 Terminal 42 Analog
Output
Parameter 7-00 Speed PID Feedback
Source
Table 6.4 Speed Close Loop
6
6
40
®
VLT
AutomationDrive FC 360
Application
[103] Motor Current
Industrial washing machines, conveyors.
Parameter 0-16 Application Selection is set to [5] Multi Speed.
[1] 24 V encoder
Description
For applications with 8 different speeds by digital input. By using
another digital input, 16 speeds are possible.
+24V 12
+10V 50
Parameter settings
Parameter
Parameter 1-00 Configuration Mode
Parameter 3-00 Reference Range
Parameter 3-15 Reference 1 Source
Parameter 4-14 Motor Speed High Limit
[Hz]
Parameter 5-10 Terminal 18 Digital Input
Parameter 5-12 Terminal 27 Digital Input
Parameter 5-13 Terminal 29 Digital Input
Parameter 5-14 Terminal 32 Digital Input
Parameter 5-15 Terminal 33 Digital Input
Parameter 6-70 Terminal 45 Mode
Parameter 6-71 Terminal 45 Analog
Output
Parameter 6-90 Terminal 42 Mode
Parameter 6-91 Terminal 42 Analog
Output
Table 6.5 Multi-speed
Danfoss A/S © 03/2017 All rights reserved.
FC 360
DI1
18
Start
DI2
19
Coast inverse
DI3
27
DI4
29
Pre set ref bit 0
DI5
3
1
DI6
3
2
Pre set ref bit 1
DI7
3
3
Pre set ref bit 2
COM 20
AI1
53
54
AI2
COM 55
AO1 4
2
AO2 4
5
1
2
R1
3
4
5
R2
6
Option/value
[0] Speed Open Loop
[0] Min–Max
[0] No Function
50.0 Hz
[8] Start
[2] Coast Inverse
[16] Preset ref bit 0
[17] Preset ref bit 1
[18] Preset ref bit 2
[0] 0–20 mA
[100] Output frequency
[0] 0–20 mA
[103] Motor Current
MG06A702