5. PARAMETERS
(2) Details list
Classifi-
No.
Symbol
cation
0
*BPS
Serial communication function selection, alarm history clear
Used to select the serial communication baudrate, select various
communication conditions, and clear the alarm history.
1
SIC
Serial communication time-out selection
Set the time-out period of the communication protocol in [s] unit.
Setting "0" disables time-out check.
2
*OP1
Function selection 1
Used to select the protocol of serial communication.
Name and Function
0
Serial baudrate selection
0: 9600 [bps]
1: 19200[bps]
2: 38400[bps]
3: 57600[bps]
Alarm history clear
0: Invalid
1: Valid
When alarm history clear is made valid,
the alarm history is cleared at next power-on.
After the alarm history is cleared, the setting
is automatically made invalid reset to "0".
Serial communication response delay time
0: Invalid
1: Valid, reply sent after delay time of 800 s or more
0
0
0
Protocol checksum selection
0: Yes (checksum added)
1: No (checksum not added)
www.dadehpardazan.ir 88594014-15
5 - 16
Initial
Setting
Unit
Value
Range
0000
Refer to
name
and
function
column.
0
0
s
1
to
60
0000
Refer to
name
and
function
column.