5. PARAMETERS
Classifi-
No.
Symbol
cation
20
INP
In-position range
Used to set the droop pulse range in which the in-position (INP) will
be output to the controller. Make setting in the feedback pulse unit
(parameter No. 6).
For example, when you want to set 10 m in the conditions that the
ballscrew is direct coupled, the lead is 10mm (0.39inch), and the
feedback pulses are 8192 pulses/rev (parameter No. 6 : 1), set "8" as
indicated by the following expression:
10
10
21
MBR
Electromagnetic brake sequence output
Used to set a time delay (Tb) from when the electromagnetic brake
interlock (MBR) turns off until the base circuit is shut off.
22
For manufacturer setting
Do not change this value by any means.
23
*OP1
Optional function 1
Used to make the servo forced stop function invalid.
24
*OP2
Optional function 2
Used to select slight vibration suppression control and motor-less
operation
Name and Function
6
10
8192
8.192
3
10
0
0
Servo forced stop selection
0: Valid (Use the forced stop (EM1).)
1: Invalid (Do not use the forced stop (EM1).)
Encoder cable selection
0: 2-wire type (when MR-JCCBL
1: 4-wire type (when MR-JC4CBL
0
0
Slight vibration suppression control selection
Made valid when auto tuning selection is
set to "0002" in parameter No.8.
Used to suppress vibration at a stop.
0: Invalid
1: Valid
Motor-less operation selection
0: Invalid
1: Makes motor-less operation valid.
When motor-less operation is made valid, signal output or
status display can be provided as if the servo motor is running
actually in response to the servo system controller command,
without the servo motor being connected.
Motor-less operation is performed as in the motor-less
operation using the MR Configurator (servo configuration software).
(Refer to Section 5.2.4.)
www.dadehpardazan.ir 88594014-15
8
Automatically switched on internally
M-L/H is used)
M-H is used)
5 - 8
Initial
Setting
Unit
Value
Range
100
pulse
0
to
50000
100
ms
0
to
1000
0001
0000
Refer to
name
and
function
column.
0000
Refer to
name
and
function
column.