Checking The Ionisation Current; Checking The Flue Gas Discharge/Air Supply Connections; Checking The Combustion - REMEHA Quinta Ace Installation, User And Service Manual

Table of Contents

Advertisement

Fig.44
Checking flue gas discharge/air
supply connections
7625116 - v.04 - 17012017
10.3.3

Checking the ionisation current

1. Check the ionisation current at full load and at part load.
See
Manual for the control panel.
The value is stable after 1 minute.
2. Clean or replace the ionisation/ignition electrode if the value is lower
than 4 µA.
10.3.4

Checking the flue gas discharge/air supply connections

1. Check the flue gas discharge and air supply connections for condi­
tion and tightness.
AD-0000223-01
10.3.5

Checking the combustion

Combustion is checked by measuring the O
gas outlet duct.
10 Maintenance
/CO
percentage in the flue
2
2
57