REMEHA Quinta Ace Installation, User And Service Manual page 46

Table of Contents

Advertisement

9 Settings
Parameter
Text display
AP006
The appliance will report low water pressure below this
value
AP008
The appliance will wait x sec (0=off) for the release
contact to close in order to start the burner
AP009
Burning hours before raising a service notification
AP010
The type of service needed based on burn and
powered hours
AP011
Hours powered to raise a service notification
AP073
Outdoor temperature: upper limit for heating
AP074
The heating is stopped. Hot water is maintained. Force
Summer Mode
AP079
Inertia of the building used for heat up speed
AP080
Outside temperature below which the antifreeze
protection is activated
AP102
Configuration of the boiler pump as zone pump or
system pump (feed lowloss header)
AP110
Parameter to activate the 2nd return sensor
CP000
Maximum Flow Temperature setpoint zone
CP010
Zone flow temperature setpoint, used when the zone is
set to a fixed flow setpoint.
CP020
Functionality of the zone
CP060
Wished room zone temperature on holiday period
CP070
Max RoomTemperature limit of the circuit in reduced
mode, that allows switching to comfort mode
CP200
Manually setting the RoomTemperature setpoint of the
zone
CP210
Comfort footpoint of the temperature of heat curve of
the circuit
CP220
Reduced footpoint of the temperature of heat curve of
the circuit
CP230
Heating curve temperature gradient of the zone
CP240
Adjustment of the influence of the zone room unit
CP340
Type of Reduced Night Mode, stop or maintain heating
of circuit
CP470
Setting of the screed drying program of the zone
CP480
Setting of the start temperature of the screed drying
programm of the zone
46
Adjustment range
0 bar - 7 bar
0 Sec - 255 Sec
0 Hours - 131070 Hours
0 = No service notification
1 = Custom service notification
2 = ABC service notification
24 Hours - 131070 Hours
1.5 °C - 60 °C
0 = Off
1 = On
0 - 255
-32 °C - 10 °C
0 = No
1 = Yes
0 = Inactive
1 = Active
0 °C - 90 °C
0 °C - 90 °C
0 = Disable
1 = Direct
2 = Mixing Circuit
3 = Swimming pool
4 = High Temperature
5 = Fan Convector
6 = Domestic Hot Water tank
7 = Electrical Domestic Hot Water
8 = Time Program
9 = ProcessHeat
10 = Domestic Hot Water Layered
11 = Domestic Hot Water Boiler Internal
tank
5 °C - 20 °C
5 °C - 30 °C
5 °C - 30 °C
15 °C - 90 °C
15 °C - 90 °C
0 - 4
0 - 10
0 = Stop heat demand
1 = Continue heat demand
0 Days - 30 Days
20 °C - 50 °C
160
0.7
0
17400
2
17400
22
0
0
0
0
0
90
80
1
6
15
20
15
15
2.5
3
0
0
20
7625116 - v.04 - 17012017