Quinta Ace
Nominal input (Qn) for central heating operation (Hs) G31 (Propane)
Full load central heating efficiency (Hi) (80/60°C) (92/42/EEC)
Full load central heating efficiency (Hi) (50°C/30°C) (EN15502)
Low load central heating efficiency (Hi) (return temperature 60°C)
Part load central heating efficiency (92/42/EEC) (return temperature
30°C)
(1) Factory setting.
Tab.4
Gas and flue gas data
Quinta Ace
Gas inlet pressure G20 (H gas)
Gas inlet pressure G31 (propane)
Gas consumption G20 (H gas)
Gas consumption G31 (propane)
BREEAM NO
X
Flue gas mass flow rate
Flue gas temperature
Maximum counter pressure
(1) Gas consumption based on lower heating value under standard conditions: T=288.15 K, p=1013.25 mbar. Gag 30.33; G25 29.25; G31
3
88.00 MJ/m
Tab.5
Central heating circuit data
Quinta Ace
Water content
Water operating pressure
Water operating pressure (PMS)
Water temperature
Operating temperature
Pressure drop secondary circuit (ΔT=20 K)
Tab.6
Electrical data
Quinta Ace
Supply voltage
Power consumption – full load
Power consumption – low load
Power consumption – standby
Electrical protection index
Fuses
7625116 - v.04 - 17012017
(1)
(1)
min. - max.
kW
%
%
%
%
min. - max.
mbar
min. - max.
mbar
min. - max.
3
m
/h
min. - max.
3
m
/h
mg/kWh
min. - max.
kg/h
g/s
min. - max.
°C
Pa
l
min
bar
max
bar
max
°C
max
°C
mbar
VAC
max
W
min
W
min
W
IP
Main
A
PCU
A
3 Technical specifications
160
43.4 - 169.6
97.5
103.6
98.4
108.5
160
17 - 25
37 - 50
3.4 - 16.5
1.4 - 6.3
36
57 - 277
16 - 77
32 - 66
200
160
17
0.8
4.0
110
90
170
160
230
275
47
5.3
IPX1B
6.3
1.6
13