FX Series Programmable Controller
6.18

Error Code Tables

Error Detection
Device
D8061
PLC Hardware
error
Error Detection
Device
D8062
PC/HPP
communication
error
(Not FX
, FX
)
1S
1N
Error Detection
Device
D8063
Serial
communication
errors
Stored Error
Number
0000
No error
6101
RAM error
6102
Operation circuit error
6103
I/O bus error (M8069 = ON)
6104
Extension unit 24V failure (M8069=ON)
6105
Watch Dog Timer error
Stored Error
Number
0000
No error
6201
Parity/ overrun/ framing error
6202
Communications character error
6203
Communication data sum check error
6204
Data format error
6205
Command error
Stored Error
Number
0000
No error
6301
Parity/ overrun/ framing error
6302
Comms character error
6303
Comms data sum check error
6304
Comms data format error
Command error
Computer link - received command
6305
other than GW (global) when station
number was FF
6306
Watchdog timer error
6312
Parallel link character error
6313
Parallel link data sum check error
6314
Parallel link data format error
Associated Meaning
Associated Meaning
Associated Meaning
Diagnostic Devices 6
FX
FX
FX
1S
1N
2N
Action
Check the cable
connection between the
extension unit/block and
the PLC
Scan time has exceeded
the WDT time value set
in D8000. Check user
program.
Action
Check the cable
connection between the
programming device and
the PLC
Note
Check communication
settings, parameters and
applicable devices.
(Computer link, N:N
network, Parallel link
etc.)
Refer to FX
Communication Users
Manual for wiring
techniques