6.7
Interrupt Control Flags
(M8050 to M8059 and D8050 to D8059)
Diagnostic
Device
M8050 (-)
I00o disable
M8051 (-)
I10o disable
M8052 (-)
I20o disable
M8053 (-)
I30o disable
M8054 (-)
I40o disable
M8055 (-)
I50o disable
M8056 (-)
I6oo disable
(Not FX
, FX
1S
1N
M8057 (-)
I7oo disable
(Not FX
, FX
1S
1N
M8058 (-)
I8oo disable
(Not FX
, FX
1S
1N
M8059(-)
I010 to I060
disabled as a
single group
(Not FX
, FX
1S
1N
For symbol key see page 6-1.
Operation
When the EI (FNC 04)
instruction is driven in the
user program, all interrupts
are enabled unless the
special M devices noted
here are driven ON. In that
case for each special M coil
that is ON, the associated
interrupt is disabled, i.e. will
not operate.
Note oo denotes all types of
)
that interrupt
)
)
I010 ~ I060 is disabled for
high speed counter interrupt
(FNC53)
When this flag is ON, the
associated interrupt is
disabled and therefore will
)
not operate.
FX
FX
1S
Diagnostic
Device
D8050 -D8059 Reserved
Diagnostic Devices 6
FX
FX
1N
2N
2NC
Operation
6-12