Asc (Fnc 76) - Mitsubishi FX1S Series Programming Manual

Melsec-f
Hide thumbs Also See for FX1S Series:
Table of Contents

Advertisement

FX Series Programmable Controlers
5.8.7

ASC (FNC 76)

Mnemonic
ASC
FNC 76
(
code
ASCII
conversion)
16 BIT OPERATION
The source data is converted to its associated ASCII codes. The codes are then stored in the
destination devices D, see example shown below.
D
D300
D301
D302
D303
Note: ASCII Char cannot be entered from a hand held programmer.
Function
An entered
Alphanumeric data e.g.
alphanumeric
0-9, A - Z and a - z etc.
string can be
Note: Only one, 8
converted to its
character string may be
ASCII codes
entered at any one
time.
32 BIT OPERATION
Byte
High
58 (X)
36 (6)
4D (M)
21 (!)
Operands
S
T, C, D
Note:
uses 4 consecutive
devices
PULSE-P
Operation:
The source data string S consists of up to 8
ch a r a c te r s ta k e n fr o m t h e p ri n ta b le A S C I I
character (Char) set. If less than 8 Char are used,
the difference is made up with null Char (ASCII
00).
Low
46 (F)
2D (-)
34 (4)
52 (R)
Applied Instructions 5
FX
FX
FX
1N
2N
1S
Program steps
D
1
ASC
: 7 steps
5-110
FX
2NC

Advertisement