Mitsubishi FX1S Series Programming Manual page 368

Melsec-f
Hide thumbs Also See for FX1S Series:
Table of Contents

Advertisement

FX Series Programmable Controller
Error Detection
Device
D8064
Parameter
error
Error Detection
Device
D8065
Syntax error
Stored Error
Number
0000
No error
6401
Program sum check error
6402
Memory capacity setting error
6403
Latched device area setting error
6404
Comment area setting error
6405
File register area setting error
6406 - 6408 Reserved
6409
Other setting error
Stored Error
Number
0000
No error
Incorrect instruction/ device symbol/
6501
device number combination
No timer or counter coil before setting
6502
value
1)No setting value following either a timer
or a counter coil
6503
2)Insufficient number of operands for an
applied instruction
1)The same label number is used more
than once
6504
2)The same interrupt input or high speed
counter input is used more than once
Device number is outside the allowable
6505
range
6506
Invalid applied instruction
Invalid Pointer device [P] assignment for
6507
Jump or Call instruction
Invalid Interrupt pointer device [I]
6508
assignment
6509
Other error
6510
MC nesting (N) number error
The same interrupt input or high speed
6511
counter input is used more than once
Associated Meaning
Associated Meaning
Diagnostic Devices 6
Action
STOP the PLC, check
parameter, if incorrect
change to a suitable
value
Action
During programming,
each instruction is
checked as it is entered.
If a syntax error is
detected, re-enter the
instruction correctly
6-24

Advertisement

Table of Contents
loading

This manual is also suitable for:

Fx1n seriesFx2nc seriesFx2n series